Wire for Water Heater (Geyser) — Size & Flame Grade per IS 694:2010

For a 3 kW domestic storage geyser drawing approximately 13 A continuous on a 230 V single-phase supply, the canonical recommendation on a dedicated 16 A circuit is 2.5 sqmm Class 5 flexible copper, FR or HRFR grade per IS 694:2010, sized using IS 3961:2024 ampacity tables and capped at the NBC 2016 Part 8 §3.4 voltage-drop limit of 3 %. For a 4.5 kW instant geyser at ~20 A move to 4 sqmm copper on a 25 A MCB, and for a 6 kW commercial unit at 27 A move to 6 sqmm copper on a 32 A MCB. This page is a third-party comparison reference.

The Sizing Table — Geyser kW to Cable

Water HeaterTypeContinuous Amps (230 V)Recommended MCBRecommended CableFlame Grade
3 kW (15 L / 25 L storage)Storage13 A16 A2.5 sqmm Class 5 CuFR / HRFR
3 kW instantInstant tank-less13 A16 A2.5 sqmm Class 5 CuHRFR (high ambient)
4.5 kW instantInstant tank-less20 A25 A4 sqmm Class 5 CuHRFR / FR-LSH
6 kW (commercial / hotel)Storage / instant27 A32 A6 sqmm Class 5 CuHRFR / FR-LSH
9 kW (3Ø)Industrial13 A per phaseTPN 16 A4-core 2.5 sqmm armouredIS 1554 Pt 1 FR
Bathroom geysers in India almost always sit in a hot, humid pocket above the shower — pick HRFR (85 °C HR PVC) wherever the cable runs through false ceilings or shaft risers.

Decision Tree — Load × Length × Ambient × Flame

  1. Read the geyser nameplate for kW. Convert to amps: A = kW × 1000 ÷ 230 (single-phase). 3 kW → 13 A; 4.5 kW → 19.6 A; 6 kW → 26.1 A.
  2. Apply IS 3961:2024 base ampacity (PVC-insulated copper in conduit). 2.5 sqmm = 23 A reference, 4 sqmm = 30 A, 6 sqmm = 38 A.
  3. Derate for ambient. Bathroom shaft and false-ceiling routes commonly hit 45 °C — apply IS 3961:2024 Table 5 factor (~0.87 at 45 °C for 70 °C PVC, higher for 85 °C HR PVC).
  4. Voltage drop. NBC 2016 Part 8 §3.4 limits total drop to 3 %. For 13 A on 2.5 sqmm at 15 m: drop ~2.0 %.
  5. Flame grade per the next section.

For a numeric run-through, use /tools/cable-size-calculator and the derating tables in /learn/is-3961-ampacity-chart.

Flame-Grade Selection (NBC 2016 Part 4)

Building ClassStandardMandatory Grade
G+3 residentialIS 694:2010FR
G+4 to G+7 residential / commercialIS 694:2010FR-LSH (HCl < 15 %)
Hospital, hotel, airport, metroIS 17048:2018HFFR (HCl < 0.5 %)
Bathroom shaft / hot duct riser, any buildingIS 694:2010 (HR PVC)HRFR (85 °C continuous)
HRFR is the practical default for geyser circuits in India because the cable typically traverses a hot, humid shaft. Note: HRFR is a Reaction-to-Fire grade — it is not Fire Survival cable per the project guide §14 locked rule.

Brand Options — 2.5 sqmm Class 5 Cu HRFR (3 kW Geyser)

BrandSKU examplePackPrice
Finolex2.5 sqmm FR flexible, 90 m90 mSee live price
HavellsLife Line Plus S3 HRFR 2.5 sqmm90 mSee live price
KEIHomecab HRFR 2.5 sqmm90 mSee live price
National Cables2.5 sqmm HRFR flexible90 mSee live price
PolycabGreen Wire HFFR 2.5 sqmm90 mSee live price
RR KabelFirex FR-LSH 2.5 sqmm90 mSee live price
Listed alphabetically. Verify the BIS standard mark and CM/L number on the jacket at bis.gov.in.

Common Mistakes — Geyser Wiring

  • Using 1.5 sqmm for a 3 kW geyser. 13 A continuous on 1.5 sqmm exceeds the NBC 2016 voltage-drop limit on most apartment wall-runs and runs the conductor near its thermal limit.
  • Specifying plain FR in a G+4+ apartment. NBC 2016 mandates FR-LSH minimum from four storeys upwards.
  • Using 70 °C PVC FR cable in a hot bathroom shaft. HRFR (85 °C HR PVC) per IS 694:2010 is the correct pick because the shaft can sit at 45–55 °C in summer.
  • No dedicated MCB. A 13 A geyser must not share a 6 A lighting MCB. Use a dedicated 16 A MCB and 30 mA RCBO for shock protection.
  • Skipping the BIS CM/L verification. Look up the licence number printed on the jacket at bis.gov.in/standard-mark-licence.

Frequently asked questions

What wire for a 3 kW geyser?
2.5 sqmm Class 5 flexible copper, FR or HRFR per IS 694:2010, on a 16 A dedicated MCB. The 13 A continuous load fits comfortably inside the IS 3961:2024 ampacity of 23 A for 2.5 sqmm copper in conduit, with NBC 2016 voltage-drop margin.
Can I use 1.5 sqmm for an instant water heater?
Only for units below ~2.4 kW (10 A). For a 3 kW instant geyser at 13 A, 1.5 sqmm is not compliant — the IS 3961:2024 base ampacity of 1.5 sqmm copper is 17 A, but after derating and the NBC 2016 3 % voltage-drop cap, 2.5 sqmm is the correct minimum.
What size cable for a 4.5 kW instant geyser?
4 sqmm Class 5 copper, HRFR or FR-LSH per IS 694:2010, on a 25 A MCB. The continuous load of 19.6 A approaches the IS 3961:2024 derated ampacity of 2.5 sqmm, so step up to 4 sqmm (reference 30 A).
What cable for a 6 kW geyser?
6 sqmm Class 5 copper on a 32 A MCB. At 26.1 A continuous, IS 3961:2024 sizing demands the 38 A reference ampacity of 6 sqmm copper after typical 0.87 derating.
Should geyser wiring be FR, FR-LSH, HRFR or HFFR?
FR for G+3. FR-LSH for G+4 and above per NBC 2016 Part 4. HFFR (IS 17048:2018) for hospitals, airports, metro stations. HRFR for any installation where the cable passes through a hot bathroom shaft — it tolerates 85 °C continuous.
Does the geyser earth wire need to match the phase size?
For phase up to 16 sqmm the earth conductor matches the phase size, per NBC 2016 Part 8 §1.4 / IS 3043. A 2.5 sqmm geyser circuit needs a 2.5 sqmm green earth.
What is the difference between FR and HRFR for a geyser?
Both are IS 694:2010 Reaction-to-Fire grades. FR uses 70 °C PVC; HRFR uses 85 °C HR PVC, which is essential when the cable traverses bathroom shafts that reach 50 °C in summer. Neither is Fire Survival cable.
Do I need a 3-core or single-core cable to the geyser?
A 3-core flexible (phase + neutral + earth) is standard for the geyser appliance flex from the wall isolator to the unit; the wall-buried sub-circuit is run as separate single-cores in conduit per NBC 2016 Part 8.
Class 2 or Class 5 conductor for geyser wiring?
Class 5 (flexible) per IS 8130:2013 is the practical default for a geyser flex; Class 2 (stranded) is acceptable for the fixed wall run. Both are recognised in IS 694:2010.
Can I run the geyser off the bathroom 6 A socket?
No. A 3 kW geyser draws 13 A — beyond the 6 A socket rating. NBC 2016 Part 8 requires a dedicated 16 A circuit and a 30 mA RCBO for any wet-area heating appliance.
Is HFFR worth the extra cost for a domestic geyser?
Only if the building is hospital-class or the spec demands halogen-free per IS 17048:2018. For ordinary G+3 to G+7 housing, HRFR or FR-LSH per IS 694:2010 is sufficient and far more cost-effective.
How do I verify BIS certification on the cable?
Every metre of the jacket must print "ISI", "IS 694:2010", manufacturer name and a CM/L licence number. Verify the CM/L at bis.gov.in/standard-mark-licence before installation.
METHODOLOGY

Updated weekly by the cablepriceindia.com price-research desk. Last verified: 17 July 2026. Sources cited inline. We are an independent price-discovery service. Verify any BIS Conformity Marking Licence (CM/L) at bis.gov.in.