HomeReference › IS 3961 Ampacity
IS 3961 Part 2 — PVC Insulated Cables at 40°C Ambient

IS 3961 Cable Ampacity & Voltage Drop Reference

Current carrying capacity (ampacity) for PVC insulated copper conductor cables. IS 3961 Part 2 Table 4. 40°C ambient, 70°C conductor operating temperature. Apply derating factors for conduit, bunching, and high ambient temperature installations.

How to use this table: (1) Calculate full-load current from load watts ÷ (voltage × power factor). (2) Apply derating factor for installation method. (3) Design current = FLA ÷ derating factor. (4) Select cable size where IS 3961 rating ≥ design current. (5) Verify voltage drop ≤ 5% over the run length using the voltage drop column.

IS 3961 Part 2 — Current Carrying Capacity & Voltage Drop

PVC insulated, copper conductor. 40°C ambient, 70°C conductor. Voltage drop in mV/A/m (millivolts per amp per metre of run).

Size
(mm²)
Clipped Direct (A)In Conduit (A)Voltage Drop (mV/A/m)
1φ / 2-wire3φ / 3-wire1φ / 2-wire3φ / 3-wireSingle phaseThree phase
1 mm²131111942.80037.065
1.5 mm²1614141229.60025.634
2.5 mm²2219181618.44015.969
4 mm²2925242111.74010.167
6 mm²373231277.8206.772
10 mm²504442364.6804.053
16 mm²665756492.9402.546
25 mm²877573631.8781.626
35 mm²1079390771.3421.162
50 mm²133116112960.9440.818
70 mm²1691471431220.6740.584
95 mm²2051791741500.4940.428
120 mm²2362072011730.3920.339
150 mm²2722382342010.3160.274
185 mm²3122732682320.2560.222
240 mm²3693233212790.1970.171
IS 3961 Part 2 Table 4. PVC insulated, copper conductor, 40°C ambient, 70°C max conductor temp. Voltage drop = 2ρL/A (single phase) or √3ρL/A (three phase). Resistance at 70°C.

Derating Factors — IS 3961 Part 2

Installation MethodDerating FactorNotes
Open air / clipped direct1.00No derating. Full rated current.
In conduit or trunking0.8020% derating. Most common installation.
Bunched — 2 cables in tray0.8515% derating.
Bunched — 3 cables in tray0.7921% derating.
Bunched — 4–6 cables in tray0.7525% derating.
Bunched — 7–9 cables in tray0.7030% derating.
Bunched — 10–12 cables in tray0.6733% derating.
Buried direct in ground (20°C soil)0.95IS 3961 Part 3.
Ambient 30°C (correction factor)1.07Better than 40°C design base.
Ambient 45°C (correction factor)0.94Derating for hot climates.
Ambient 50°C (correction factor)0.87Common in Indian industrial sites.
IS 3961 Part 2. For multiple derating factors, multiply them together (e.g., conduit 0.80 × high ambient 0.87 = 0.696 combined factor).

Worked Example — Cable Sizing per IS 3961

Load3 kW motor, 415V 3-phase, PF = 0.85
Step 1: Full Load CurrentFLA = 3000 ÷ (√3 × 415 × 0.85) = 4.92 A
Step 2: Design Current (with 1.25× starting)Design = 4.92 × 1.25 = 6.15 A
Step 3: Apply derating (conduit 0.80)Required capacity = 6.15 ÷ 0.80 = 7.69 A
Step 4: Select cable from IS 39611.5mm² in conduit = 12A ≥ 7.69A ✓
Step 5: Verify voltage drop (30m run)VD = √3 × 4.92 × 30 × 14.8 mV/A/m ÷ 1000 = 3.77V = 0.91% ✓ (<5%)
Result1.5mm² FR IS 694:2010 in conduit — compliant per IS 3961

Ready to specify your project?

Cable Size Calculator →Build Project BOQ →
📋 List your prices