IS 3961:2024 Ampacity Chart — Indian Standard Current Carrying Capacity Reference
The current-carrying capacity (ampacity) of an Indian cable depends on five variables: (a) conductor material — copper vs aluminium, (b) cross-section in sqmm, (c) conductor class — Class 2 stranded vs Class 5 fine-stranded per IS 8130:2013, (d) installation method — single-core in air, in conduit, in trefoil, multi-core, or buried, and (e) ambient-temperature derating from the 30 °C (in air) / 20 °C (buried) reference. The master tables below give the published IS 3961:2024 values for the full 1.0–400 sqmm range. Voltage drop is tabulated in mV/A/m — the convention every Indian wiring manual uses — so the worked example at the bottom of this page can be copied into any BOQ.
CablePriceIndia.com is a third-party comparison reference. The values are reproduced from IS 3961:2024 (the current revision) and, where the older IS 3961 Part 2 is the only published value, the older edition is cited explicitly. Always verify the standard against the current edition on bis.gov.in before sealing a design.
How IS 3961:2024 ampacity values are derived
The ampacity of a cable is the steady-state current it can carry without exceeding its conductor temperature limit. The standard solves a heat-balance equation: the I²R loss in the conductor must equal the heat that the cable surface can dissipate into the surrounding medium (air, conduit wall, soil) at the assumed ambient temperature.
The three inputs to the calculation are:
- Reference ambient temperature. IS 3961:2024 uses 30 °C for cables in air and 20 °C for cables buried direct in soil. Every published value in the master tables below assumes the reference. Field temperatures above the reference require a derating factor — see §6.
- Conductor temperature limit (the "hot-spot" cap).
- Conductor resistance. The R in I²R is taken from IS 8130:2013 — the conductor standard. Class 2 (stranded, fixed installation) has lower DC resistance per metre than Class 5 (fine-stranded, flexible) at the same sqmm, because Class 5 packs more, thinner strands and the geometry slightly increases the effective resistance. Class 5 ampacity is therefore 2–4 % lower than Class 2 at the same cross-section.
International cross-reference: IEC 60364-5-52 ("Selection and erection of electrical equipment — Wiring systems") publishes parallel ampacity tables that IS 3961 is broadly aligned with for installation methods A1, B1, C, D and E. Where IS 3961:2024 differs (typically the buried-direct values, which assume Indian soil thermal resistivity of 1.5 K·m/W), the IS value governs Indian designs.
> Reaction to Fire ≠ Fire Survival. FR, FR-LSH, HFFR, HRFR are Reaction to Fire classifications (smoke / halogen / flame-spread behaviour during a fire). They do not change the cable's steady-state ampacity, because the conductor and insulation temperature limits are unchanged. A Fire Survival / Circuit Integrity cable (IEC 60331 / BS 6387) is a different product entirely and has its own derating curves while in-fire — not relevant to normal sizing.
Master Table 1 — Copper conductor ampacity (IS 3961:2024)
Reference 30 °C ambient, single-phase or three-phase a.c. at 50 Hz, plain PVC (70 °C conductor limit). For XLPE (90 °C) multiply ampacity by ≈ 1.20. Values are for Class 2 conductor; Class 5 ampacity is ≈ 3 % lower (see §10 FAQ).
| Size sqmm | Single core in air (A) | Single core in conduit (A) | 2-core in air (A) | 2-core in conduit (A) | 3/4-core in air (A) | 3/4-core in conduit (A) | Voltage drop mV/A/m |
|---|---|---|---|---|---|---|---|
| 1.0 | 19 | 14 | 17 | 13 | 15 | 11 | 44 |
| 1.5 | 24 | 18 | 22 | 16 | 19.5 | 14 | 29 |
| 2.5 | 32 | 25 | 30 | 22 | 27 | 19.5 | 18 |
| 4 | 42 | 33 | 38 | 30 | 36 | 26 | 11 |
| 6 | 54 | 43 | 49 | 38 | 46 | 33 | 7.3 |
| 10 | 75 | 60 | 68 | 53 | 63 | 46 | 4.4 |
| 16 | 100 | 80 | 91 | 71 | 85 | 62 | 2.8 |
| 25 | 133 | 105 | 121 | 94 | 112 | 82 | 1.75 |
| 35 | 164 | 130 | 150 | 117 | 138 | 101 | 1.25 |
| 50 | 198 | 158 | 181 | 142 | 168 | 122 | 0.93 |
| 70 | 253 | 202 | 231 | 181 | 213 | 156 | 0.63 |
| 95 | 306 | 245 | 280 | 219 | 258 | 188 | 0.46 |
| 120 | 354 | 284 | 324 | 253 | 299 | 218 | 0.36 |
| 150 | 407 | 327 | 372 | 291 | 344 | 250 | 0.29 |
| 185 | 464 | 374 | 425 | 332 | 392 | 286 | 0.23 |
| 240 | 546 | 442 | 500 | 390 | 461 | 336 | 0.180 |
Master Table 2 — Aluminium conductor ampacity (IS 3961:2024)
Aluminium has ≈ 1.6× the resistivity of copper, so a given sqmm of aluminium carries ≈ 78 % of the equivalent copper ampacity. Aluminium becomes economical only above 16 sqmm — sizes below that exist on paper but are rare in Indian practice.
Reference 30 °C ambient, plain PVC (70 °C conductor limit). For XLPE multiply by ≈ 1.20.
| Size sqmm | Single core in air (A) | Single core in conduit (A) | 2-core in air (A) | 2-core in conduit (A) | 3/4-core in air (A) | 3/4-core in conduit (A) | Voltage drop mV/A/m |
|---|---|---|---|---|---|---|---|
| 1.5 | 18 | 14 | 17 | 12 | 15 | 11 | 47 |
| 2.5 | 25 | 19 | 23 | 17 | 21 | 15 | 29 |
| 4 | 33 | 26 | 30 | 23 | 28 | 20 | 18 |
| 6 | 42 | 33 | 38 | 30 | 36 | 26 | 12 |
| 10 | 58 | 47 | 53 | 41 | 49 | 36 | 7.1 |
| 16 | 78 | 62 | 71 | 55 | 66 | 48 | 4.5 |
| 25 | 103 | 82 | 94 | 73 | 87 | 64 | 2.85 |
| 35 | 127 | 101 | 116 | 91 | 107 | 78 | 2.05 |
| 50 | 154 | 123 | 141 | 110 | 130 | 95 | 1.50 |
| 70 | 197 | 157 | 180 | 141 | 166 | 121 | 1.05 |
| 95 | 238 | 191 | 218 | 170 | 201 | 146 | 0.77 |
| 120 | 276 | 221 | 252 | 197 | 233 | 170 | 0.63 |
| 150 | 318 | 255 | 290 | 227 | 268 | 195 | 0.51 |
| 185 | 362 | 291 | 331 | 259 | 305 | 223 | 0.41 |
| 240 | 425 | 344 | 390 | 304 | 359 | 262 | 0.32 |
| 300 | 486 | 394 | 446 | 348 | 411 | 300 | 0.26 |
| 400 | 564 | 462 | — | — | 478 | 348 | 0.21 |
Derating factors
Table values above are at reference conditions. Field installations almost always require derating. Multiply the table ampacity by all applicable derating factors to get the field ampacity.
6.1 Ambient temperature derating (cables in air, PVC 70 °C)
| Ambient °C | Derating factor (PVC) | Derating factor (XLPE 90 °C) |
|---|---|---|
| 25 | 1.06 | 1.04 |
| 30 (ref.) | 1.00 | 1.00 |
| 35 | 0.94 | 0.96 |
| 40 | 0.87 | 0.91 |
| 45 | 0.79 | 0.87 |
| 50 | 0.71 | 0.82 |
| 55 | 0.61 | 0.76 |
| 60 | 0.50 | 0.71 |
6.2 Grouping derating (multiple cables in a single conduit, tray, or trefoil)
| Number of cables / circuits | Derating factor |
|---|---|
| 1 | 1.00 |
| 2 | 0.80 |
| 3 | 0.70 |
| 4 | 0.65 |
| 6 | 0.57 |
| 9 | 0.50 |
| 12 | 0.45 |
| 16+ | 0.41 |
6.3 Soil thermal resistivity derating (buried direct)
| Soil thermal resistivity K·m/W | Derating factor |
|---|---|
| 1.0 (wet sand, river soil) | 1.13 |
| 1.5 (reference, average Indian soil) | 1.00 |
| 2.0 (clay, dry-season agricultural) | 0.91 |
| 2.5 (rocky, mixed back-fill) | 0.84 |
| 3.0 (dry sandy / desert) | 0.78 |
Voltage drop calculation
Use the mV/A/m column in the master tables. For a balanced three-phase circuit:
> Vdrop (V) = √3 × I (A) × L (m) × ZmV/A/m / 1000
For single-phase, drop the √3:
> Vdrop (V) = 2 × I (A) × L (m) × ZmV/A/m / 1000
(The factor of 2 accounts for line + neutral round-trip; the table's mV/A/m is per single conductor metre.)
The ZmV/A/m in IS 3961:2024 already includes both the resistive (R) and reactive (X) components at 50 Hz at full conductor temperature. For sizes ≥ 50 sqmm the X component is non-negligible — IS 3961:2024 Annex C splits R and X if a power-factor-corrected calculation is needed.
NBC 2016 Part 8 §3.4.5 sets the voltage-drop limit at:- ≤ 3 % between the consumer terminal and any final sub-circuit (lighting and general power)
- ≤ 5 % including the supply transformer where the user owns the transformer
IEEMA Technical Practice TP-22 reads the same limits. In practice, designers target ≤ 2 % for motor circuits to protect starting torque.
Worked example — sizing a 3 kW single-phase motor on a 30 m run
Step 1 — Full-load current. I = P / (V × pf) = 3000 / (230 × 0.85) = 15.3 A. Round up to the next standard MCB rating: 16 A. Step 2 — First cable pick from Master Table 1. 2.5 sqmm copper Class 5 (FR), in conduit: ampacity 25 A at 30 °C — passes the thermal check at 16 A. Step 3 — Voltage drop check. 2.5 sqmm copper, 18 mV/A/m, single-phase, 16 A, 30 m: Vdrop = 2 × 16 × 30 × 18 / 1000 = 17.3 V ≈ 7.5 % of 230 V.That fails NBC's 3 % limit by a wide margin. Step up.
Step 4 — Re-check with 4 sqmm. 4 sqmm copper, 11 mV/A/m, 16 A, 30 m: Vdrop = 2 × 16 × 30 × 11 / 1000 = 10.6 V ≈ 4.6 %. Still fails. Step 5 — Re-check with 6 sqmm. 6 sqmm copper, 7.3 mV/A/m, 16 A, 30 m: Vdrop = 2 × 16 × 30 × 7.3 / 1000 = 7.0 V ≈ 3.0 %. At the NBC limit — acceptable. Final spec: 6 sqmm copper Class 5 FR (or FR-LSH if the run passes through a basement / shaft of an NBC G+4+ residential building, per NBC 2016 Part 4 §A-3.4.13).The lesson: at long runs, voltage drop — not ampacity — sets the cable size. The 2.5 sqmm passes the heat check at 16 A but fails the volt-drop check by a factor of 2.5×. Always run both.
How to use this chart
- Compute the design current. I = load / (V × pf) for motors; sum of branch currents × diversity for distribution boards. Add a 25 % continuous-load factor for circuits feeding a continuously-loaded device (≥ 3 hours, per NBC 2016 §3.4.4).
- Pick the column — match installation method (single-core in air, in conduit, multi-core in conduit, buried).
- Select a candidate row whose ampacity ≥ design current.
- Apply derating factors from §6 (ambient × grouping × soil). If the derated ampacity drops below the design current, step up one size and re-test.
- Voltage-drop check against the NBC 3 % limit. Step up further if it fails. The worked example above shows this is often the binding constraint on long runs.
- Round up to a standard size, never down.
Frequently asked questions
What is the current-carrying capacity of 2.5 sqmm copper cable?
What is the current-carrying capacity of 4 sqmm cable?
What is the formula for ampacity calculation?
How do I derate cable for high ambient temperature?
What is the voltage drop in 2.5 sqmm copper cable per metre?
What size cable do I need for a 32 A circuit?
What size cable for an air conditioner?
What is the difference between Class 2 and Class 5 ampacity?
Does FR-LSH have a different ampacity than FR?
What is the ampacity of 1.5 sqmm aluminium vs copper?
How does cable installation method (conduit vs in air) affect ampacity?
What is IS 3961:2024 (or Part 2)?
Updated weekly by the cablepriceindia.com price-research desk. Last verified: 12 July 2026. Sources cited inline. We are an independent price-discovery service. Verify any BIS Conformity Marking Licence (CM/L) at bis.gov.in.
Save this price list as PDF
CablePriceIndia is a B2B reference. To save the price list we verify you're a business buyer. Free, once-off. Unlocks every price page for 48 hours.