Wire for Air Conditioner — Size, FR Grade, IS 3961:2024 Sizing
For a 1.5-ton split AC drawing roughly 8–10 A continuous (rated current) and 18 A LRA at start, the canonical recommendation on a dedicated 16 A circuit is 2.5 sqmm Class 5 flexible copper, FR grade, to IS 694:2010, sized using the IS 3961:2024 ampacity tables and the NBC 2016 Part 8 §3.4 voltage-drop limit of 3 % for final sub-circuits. For 2-ton and 2.5-ton inverter units, step up to 4 sqmm Class 5 FR copper on a 20 A or 25 A MCB. This page is a third-party comparison reference; it does not promote any single brand.
The Sizing Table — AC Tonnage to Cable
| AC Tonnage | Type | Continuous Amps (230 V, 1Ø) | LRA / Start Amps | Recommended MCB | Recommended Cable | Flame Grade |
|---|---|---|---|---|---|---|
| 1.0 T | Split / Window | 6–8 A | 12 A | 10 A | 1.5 sqmm Class 5 Cu | FR (IS 694:2010) |
| 1.5 T (fixed-speed) | Split | 8–10 A | 18 A | 16 A | 2.5 sqmm Class 5 Cu | FR / HRFR |
| 1.5 T (5-star inverter) | Split | 4–14 A variable | 14 A peak | 16 A | 2.5 sqmm Class 5 Cu | FR / HRFR |
| 2.0 T | Split / Cassette | 11–13 A | 24 A | 20 A | 4 sqmm Class 5 Cu | HRFR / FR-LSH |
| 2.5 T | Split / Tower | 14–16 A | 30 A | 25 A | 4 sqmm Class 5 Cu | HRFR / FR-LSH |
| 3.0 T | Cassette / Ducted | 16–18 A | 36 A | 32 A | 6 sqmm Class 5 Cu | HRFR / FR-LSH |
| 5.0 T | Ducted (3Ø) | 8–10 A per phase | 22 A per phase | 4P 20 A | 4-core 4 sqmm armoured | FR (IS 1554-1) |
Decision Tree — Load × Length × Ambient × Flame
Use this in order:
- Read the AC nameplate. Note rated current (A) and LRA. If only kW is given, divide by 0.230 kV × power-factor (0.9 for inverter, 0.85 for fixed).
- Apply the IS 3961:2024 base ampacity for the conductor type (single-core PVC-insulated copper, in conduit). 2.5 sqmm copper carries 23 A reference, 4 sqmm carries 30 A, 6 sqmm carries 38 A.
- Apply derating. For ambient above 30 °C, multiply by Table 5 of IS 3961:2024. For grouping (multiple circuits in one conduit), apply Table 7. Indian summer attic/conduit runs frequently push effective ambient to 45–50 °C; expect a derating factor of 0.82–0.87.
- Check voltage drop. NBC 2016 Part 8 §3.4 caps total drop at 3 % from meter to point. For 16 A on 2.5 sqmm copper at 20 m, drop is ~2.6 % — within limit. At 30 m, switch to 4 sqmm.
- Pick flame grade from the next section.
Use the /tools/cable-size-calculator for a quick numeric check, and the full /learn/is-3961-ampacity-chart reference table for derating factors.
Flame-Grade Selection (NBC 2016 Part 4)
| Building Class | Standard | Mandatory Grade | Why |
|---|---|---|---|
| G+3 residential | IS 694:2010 | FR | Reaction-to-Fire only; flame-retardant PVC sufficient |
| G+4 to G+7 residential / small commercial | IS 694:2010 | FR-LSH | HCl emission < 15 % to limit acid-gas damage in stairwells |
| Hospital, airport, metro, mall atrium | IS 17048:2018 | HFFR | Halogen-free, HCl < 0.5 %, low smoke |
| AC ducted run inside false ceiling, high ambient | IS 694:2010 (HR PVC, 85 °C) | HRFR | Heat-Resistant FR; PVC rated for 85 °C continuous conductor temp |
For AC circuits inside false ceilings, behind condensers, or in roof-deck conduits where ambient routinely exceeds 50 °C, HRFR (85 °C PVC) is the preferred IS 694:2010 variant. FR-LSH is mandatory in G+4+ buildings regardless.
Brand Options — 2.5 sqmm Class 5 Cu FR (1.5 T AC)
| Brand | SKU example | Pack | Price |
|---|---|---|---|
| Finolex | 2.5 sqmm FR flexible, 90 m coil | 90 m | See live price |
| Havells | Life Line Plus S3 HRFR 2.5 sqmm | 90 m | See live price |
| KEI | Homecab FR 2.5 sqmm | 90 m | See live price |
| National Cables | 2.5 sqmm FR flexible | 90 m | See live price |
| Polycab | Green Wire HFFR 2.5 sqmm | 90 m | See live price |
| RR Kabel | Firex FR-LSH 2.5 sqmm | 90 m | See live price |
Common Mistakes — AC Wiring
- Using 1.5 sqmm for a 1.5 T AC to save cost. At 18 A LRA the voltage drop on 1.5 sqmm at 15 m exceeds the NBC 2016 3 % limit and the conductor runs hot during start-up.
- Specifying plain FR in a G+4+ building. NBC 2016 mandates FR-LSH minimum in stairwell-served buildings of four storeys or more.
- Ignoring grouping derating. Three AC circuits sharing a single conduit cuts effective ampacity by ~30 % per IS 3961:2024 Table 7.
- Choosing Class 2 stranded for the indoor-unit drop. The flexible drop from the wall to the IDU should be Class 5 per IS 8130:2013 — Class 2 is for fixed building wiring, not appliance flex.
- Skipping the BIS CM/L check. The BIS standard mark plus CM/L number must be printed every metre on the jacket. Verify the licence at bis.gov.in.
Frequently asked questions
What size wire for 1.5 ton AC?
What size wire for 2 ton inverter AC?
What is the cable rating for a 5-star AC?
Should I use FR or FR-LSH for AC circuit?
What gauge wire for window AC?
Can I run the AC on the regular 6 A lighting circuit?
Does an inverter AC need a different cable than a fixed-speed AC?
What is the difference between FR and HRFR for AC wiring?
Is 4 sqmm overkill for a 1.5 T AC?
What conductor class — Class 2 or Class 5 — for AC wiring?
Do I need 3-core or single-core for split AC?
How do I verify the cable is genuine BIS-certified?
Updated weekly by the cablepriceindia.com price-research desk. Last verified: 1 July 2026. Sources cited inline. We are an independent price-discovery service. Verify any BIS Conformity Marking Licence (CM/L) at bis.gov.in.