Wire for Air Conditioner — Size, FR Grade, IS 3961:2024 Sizing

For a 1.5-ton split AC drawing roughly 8–10 A continuous (rated current) and 18 A LRA at start, the canonical recommendation on a dedicated 16 A circuit is 2.5 sqmm Class 5 flexible copper, FR grade, to IS 694:2010, sized using the IS 3961:2024 ampacity tables and the NBC 2016 Part 8 §3.4 voltage-drop limit of 3 % for final sub-circuits. For 2-ton and 2.5-ton inverter units, step up to 4 sqmm Class 5 FR copper on a 20 A or 25 A MCB. This page is a third-party comparison reference; it does not promote any single brand.

The Sizing Table — AC Tonnage to Cable

AC TonnageTypeContinuous Amps (230 V, 1Ø)LRA / Start AmpsRecommended MCBRecommended CableFlame Grade
1.0 TSplit / Window6–8 A12 A10 A1.5 sqmm Class 5 CuFR (IS 694:2010)
1.5 T (fixed-speed)Split8–10 A18 A16 A2.5 sqmm Class 5 CuFR / HRFR
1.5 T (5-star inverter)Split4–14 A variable14 A peak16 A2.5 sqmm Class 5 CuFR / HRFR
2.0 TSplit / Cassette11–13 A24 A20 A4 sqmm Class 5 CuHRFR / FR-LSH
2.5 TSplit / Tower14–16 A30 A25 A4 sqmm Class 5 CuHRFR / FR-LSH
3.0 TCassette / Ducted16–18 A36 A32 A6 sqmm Class 5 CuHRFR / FR-LSH
5.0 TDucted (3Ø)8–10 A per phase22 A per phase4P 20 A4-core 4 sqmm armouredFR (IS 1554-1)
All values are for ambient 40 °C, conduit-buried single-phase 230 V supply, run length under 20 m. Always cross-check the unit nameplate.

Decision Tree — Load × Length × Ambient × Flame

Use this in order:

  1. Read the AC nameplate. Note rated current (A) and LRA. If only kW is given, divide by 0.230 kV × power-factor (0.9 for inverter, 0.85 for fixed).
  2. Apply the IS 3961:2024 base ampacity for the conductor type (single-core PVC-insulated copper, in conduit). 2.5 sqmm copper carries 23 A reference, 4 sqmm carries 30 A, 6 sqmm carries 38 A.
  3. Apply derating. For ambient above 30 °C, multiply by Table 5 of IS 3961:2024. For grouping (multiple circuits in one conduit), apply Table 7. Indian summer attic/conduit runs frequently push effective ambient to 45–50 °C; expect a derating factor of 0.82–0.87.
  4. Check voltage drop. NBC 2016 Part 8 §3.4 caps total drop at 3 % from meter to point. For 16 A on 2.5 sqmm copper at 20 m, drop is ~2.6 % — within limit. At 30 m, switch to 4 sqmm.
  5. Pick flame grade from the next section.

Use the /tools/cable-size-calculator for a quick numeric check, and the full /learn/is-3961-ampacity-chart reference table for derating factors.

Flame-Grade Selection (NBC 2016 Part 4)

Building ClassStandardMandatory GradeWhy
G+3 residentialIS 694:2010FRReaction-to-Fire only; flame-retardant PVC sufficient
G+4 to G+7 residential / small commercialIS 694:2010FR-LSHHCl emission < 15 % to limit acid-gas damage in stairwells
Hospital, airport, metro, mall atriumIS 17048:2018HFFRHalogen-free, HCl < 0.5 %, low smoke
AC ducted run inside false ceiling, high ambientIS 694:2010 (HR PVC, 85 °C)HRFRHeat-Resistant FR; PVC rated for 85 °C continuous conductor temp
Note: HRFR is a Reaction-to-Fire grade — it is not Fire-Survival cable (FS / circuit-integrity) per the locked rule §14 of the project guide. For genuine fire-survival circuits use IS 17505 / BS 6387 cable, not HRFR.

For AC circuits inside false ceilings, behind condensers, or in roof-deck conduits where ambient routinely exceeds 50 °C, HRFR (85 °C PVC) is the preferred IS 694:2010 variant. FR-LSH is mandatory in G+4+ buildings regardless.

Brand Options — 2.5 sqmm Class 5 Cu FR (1.5 T AC)

BrandSKU examplePackPrice
Finolex2.5 sqmm FR flexible, 90 m coil90 mSee live price
HavellsLife Line Plus S3 HRFR 2.5 sqmm90 mSee live price
KEIHomecab FR 2.5 sqmm90 mSee live price
National Cables2.5 sqmm FR flexible90 mSee live price
PolycabGreen Wire HFFR 2.5 sqmm90 mSee live price
RR KabelFirex FR-LSH 2.5 sqmm90 mSee live price
Listed alphabetically. Prices are dynamic — see the live price list and verify the BIS CM/L licence printed on every coil at bis.gov.in.

Common Mistakes — AC Wiring

  • Using 1.5 sqmm for a 1.5 T AC to save cost. At 18 A LRA the voltage drop on 1.5 sqmm at 15 m exceeds the NBC 2016 3 % limit and the conductor runs hot during start-up.
  • Specifying plain FR in a G+4+ building. NBC 2016 mandates FR-LSH minimum in stairwell-served buildings of four storeys or more.
  • Ignoring grouping derating. Three AC circuits sharing a single conduit cuts effective ampacity by ~30 % per IS 3961:2024 Table 7.
  • Choosing Class 2 stranded for the indoor-unit drop. The flexible drop from the wall to the IDU should be Class 5 per IS 8130:2013 — Class 2 is for fixed building wiring, not appliance flex.
  • Skipping the BIS CM/L check. The BIS standard mark plus CM/L number must be printed every metre on the jacket. Verify the licence at bis.gov.in.

Frequently asked questions

What size wire for 1.5 ton AC?
2.5 sqmm Class 5 flexible copper to IS 694:2010, FR grade, on a 16 A MCB. The IS 3961:2024 base ampacity of 2.5 sqmm copper in conduit is 23 A; after typical derating it carries the 18 A LRA of a 1.5 T compressor with NBC 2016 voltage-drop margin.
What size wire for 2 ton inverter AC?
4 sqmm Class 5 copper, FR or HRFR, on a 20 A or 25 A MCB. The 24 A LRA and continuous 11–13 A pull demand a 30 A reference ampacity per IS 3961:2024, giving headroom for 40 °C ambient derating.
What is the cable rating for a 5-star AC?
A 5-star inverter peaks lower than its fixed-speed equivalent — a 1.5 T 5-star unit may peak at 14 A — but you still wire it to the maximum rating, so 2.5 sqmm FR copper on a 16 A MCB. IS 3961:2024 sizing is based on worst-case continuous current, not BEE star nameplate.
Should I use FR or FR-LSH for AC circuit?
FR per IS 694:2010 is sufficient in G+3 dwellings. NBC 2016 Part 4 requires FR-LSH from G+4 upwards because of stairwell smoke/acid-gas limits (HCl < 15 %). For false-ceiling runs near AC ducts where ambient is high, prefer HRFR (85 °C HR PVC).
What gauge wire for window AC?
A 1.0–1.5 T window AC at 6–10 A continuous uses 1.5–2.5 sqmm Class 5 FR copper. If the unit is on a dedicated 16 A circuit, default to 2.5 sqmm — this matches socket and MCB ratings and gives derating margin per IS 3961:2024.
Can I run the AC on the regular 6 A lighting circuit?
No. NBC 2016 Part 8 requires a dedicated final sub-circuit for any appliance over ~1.5 kW. AC compressors trip undersized lighting MCBs on start-up because the LRA is 2–3× rated current.
Does an inverter AC need a different cable than a fixed-speed AC?
Cable size is the same for the same tonnage; inverter ACs draw lower continuous current but the wire is sized to the worst-case nameplate. Inverter ACs are more sensitive to voltage drop, so respect the NBC 2016 3 % cap on long runs.
What is the difference between FR and HRFR for AC wiring?
Both are IS 694:2010 grades. FR uses 70 °C PVC; HRFR uses 85 °C HR PVC giving a higher continuous conductor temperature — useful in false-ceiling and conduit runs near AC condensers. Both are Reaction-to-Fire grades, not Fire Survival.
Is 4 sqmm overkill for a 1.5 T AC?
Generally yes for runs under 20 m on a 16 A MCB, but valid if the run exceeds 25 m or the conduit is shared with other heavy circuits. The IS 3961:2024 voltage-drop method is the correct test — not a rule of thumb.
What conductor class — Class 2 or Class 5 — for AC wiring?
Class 2 (stranded) per IS 8130:2013 for the fixed wall-buried run; Class 5 (flexible) for the appliance pigtail to the IDU. Most installers use Class 5 throughout for ease of pulling, which is acceptable per IS 694:2010.
Do I need 3-core or single-core for split AC?
Single-core (phase + neutral as separate runs) for the conduit-buried building wire; 3-core flexible (phase + neutral + earth) for the appliance flex from the isolator to the IDU. Earth conductor sizing follows NBC 2016 Part 8 §1.4.
How do I verify the cable is genuine BIS-certified?
The jacket must print "ISI", "IS 694:2010", manufacturer name, and a CM/L number every metre. Cross-check the CM/L at bis.gov.in/standard-mark-licence — counterfeit jackets fail this lookup.
METHODOLOGY

Updated weekly by the cablepriceindia.com price-research desk. Last verified: 1 July 2026. Sources cited inline. We are an independent price-discovery service. Verify any BIS Conformity Marking Licence (CM/L) at bis.gov.in.