Sourced from BIS · LME · 7 brand price lists · How prices are sourced →IS 694:2010 · IS 17048:2018 · IS 1554 · IS 7098
CablePriceIndia
REFERENCE · JULY 2026

Cable Fire Performance — FR vs FR-LSH vs HFFR vs HRFR

Indian building wire is sold in four distinct fire-performance grades: FR and FR-LSH (both certified to IS 694:2010), HRFR (IS 694:2010 with 85 °C heat-resistant PVC), and HFFR (a separate Indian standard, IS 17048:2018, also marketed as LSZH / LS0H / ZHFR). None of these four are Fire Survival cables — that is a different product class, governed by IEC 60331 / BS 6387 / IS 17505, and specifying any of the four on a fire-survival circuit is a professional-liability error. This page sets out the quantitative comparison (HCl, smoke density, oxygen index, conductor temperature), the test-method references, and the Engineering Note that distinguishes Reaction to Fire from Fire Survival.


Engineering Note — "Reaction to Fire" is NOT "Fire Survival"

> This is the most-conflated topic in Indian cable specification. Get it wrong on a tender and the consultant carries the liability.

Reaction to Fire describes how a cable behaves during a fire — smoke output, HCl evolution, flame propagation along a bunched run. It does not mean the cable continues to carry current.
  • Test methods (Reaction to Fire): IS 10810, IEC 60332-1 (single-cable flame), IEC 60332-3 (bunched-cable flame), IEC 60754-1 / 60754-2 (halogen acid gas), IEC 61034-1 / 61034-2 (smoke density).
  • Products in this category: FR (IS 694:2010), FR-LSH (IS 694:2010 with HCl < 15%), HFFR (IS 17048:2018 with HCl < 0.5%), HRFR (IS 694:2010 with 85 °C heat-resistant PVC).
Fire Survival (also called Circuit Integrity or Fire-Resistant) describes whether a cable continues to carry rated voltage through a fire — typically for 30, 60, 90 or 120 minutes at 750 °C, 950 °C or 1000 °C, with shock and water-spray phases.
  • Test methods (Fire Survival): BS 6387 (categories C, W, Z), IEC 60331-21 / 60331-25, IS 17505.
  • Products: Mineral-Insulated (MI) cables, mica-tape ceramifiable cables, FR-FS constructions. None are IS 694:2010 / IS 17048:2018 building wires.
NBC 2016 Part 4 requires both categories on different circuits in the same building. Lighting, general power and small-power use Reaction-to-Fire grades (FR / FR-LSH / HFFR by building type). Life-safety circuits — fire-pump power, lift-recall, smoke-extraction fans, PA, emergency lighting — must use Fire Survival cables to BS 6387 / IEC 60331 / IS 17505. Specifying FR-LSH or HFFR on a fire-pump feeder does not satisfy NBC 2016 and exposes the consultant of record.

The four IS 694:2010 / IS 17048:2018 grades — quantitative comparison

PropertyPlain PVCFRHRFRFR-LSHHFFR
StandardIS 694:2010 (no flame test required)IS 694:2010IS 694:2010 (HR PVC)IS 694:2010IS 17048:2018
Continuous conductor temp70 °C70 °C85 °C70 °C90 °C (typical)
Flame propagationnone specifiedIEC 60332-1IEC 60332-1IEC 60332-1 + IEC 60332-3IEC 60332-1 + IEC 60332-3
HCl emission %n/a (no limit)not regulatednot regulated< 15%< 0.5%
Smoke density (light transmittance, IEC 61034)very low (opaque)reducedreducedimproved> 60% at 3 m
Oxygen index (IS 10810 / ISO 4589)~21%≥ 29%≥ 29%≥ 29%≥ 30%
Halogen contenthighhighhighreducedhalogen-free
Use case (NBC 2016 indicative)not used for Indian residential wiringresidential up to G+3high-ambient runs, AC circuits, atticresidential G+4+, commercialhospitals, airports, metro, data centres, public assembly
- FR — IS 694:2010 baseline: oxygen index ≥ 29% and IEC 60332-1. Does not regulate HCl or smoke.
  • FR-LSH — IS 694:2010 with HCl < 15% per IS 10810 / IEC 60754 and improved smoke density.
  • HRFR — FR with heat-resistant 85 °C PVC for AC compressor circuits and high-ambient runs. Not lower-smoke than FR.
  • HFFR — separate standard IS 17048:2018, halogen-free: HCl < 0.5%, light transmittance > 60% at 3 m, oxygen index ≥ 30%, typically also IEC 60332-3 bunched-cable compliant.
  • HR-FR-LSH — 85 °C HR PVC with HCl < 15%. Polycab Green Wires only (April 2026).

HCl emission — the 30:1 ratio between HFFR and FR-LSH

The acid-gas evolution of burning PVC is the single number that drives the FR-LSH / HFFR specification choice. IS 10810 and IEC 60754-1 measure the mass percentage of HCl released when 1 g of compound is burned at 800 °C.

`` Plain PVC ████████████████████████████████ ~28–30% FR ████████████████████████████████ ~28–30% (no upper limit) FR-LSH ████████████████ < 15% (IS 694:2010 limit) HFFR ▌ < 0.5% (IS 17048:2018 limit) `

The ceiling-to-ceiling ratio between HFFR and FR-LSH is 30 : 1. HCl is acutely toxic at low concentrations and, on contact with water vapour, forms hydrochloric acid that destroys electronics, switchgear and structural steel long after extinguishment. Hospitals, airports, metro stations and data centres specify HFFR for both reasons.


Smoke density — visibility for evacuation

IEC 61034-2 measures smoke density in a 3 m × 3 m × 3 m cube as the percentage of light that transmits across the diagonal while a 1-metre cable sample burns. Higher percentage = clearer air = visible escape route.

` HFFR (IS 17048:2018) > 60% light transmittance at 3 m ████████████ FR-LSH (IS 694:2010) ~40–60% (improved over FR) ████████ FR (IS 694:2010) ~20–40% (reduced vs plain PVC) ████ Plain PVC < 20% (effectively opaque) ▍ `

In corridor evacuation, the difference between FR and HFFR is the difference between visible exit signage and an opaque smoke layer at head height. NBC 2016 Part 4 references this when mandating cable type for escape routes, atria and assembly occupancies.


When to specify which grade

The decision is driven by NBC 2016 Part 4 occupancy classification and building height. See /learn/nbc-2016-fire-safety` for the full compliance matrix; the summary below is indicative.

Building / circuit typeIndicative gradeRationale
Residential up to G+3 (Group A-1, A-2)FRNBC 2016 minimum; IS 694:2010 baseline
Residential G+4 and aboveFR-LSHSmoke + halogen reduction in stair pressurisation routes
Commercial (Group E), shopping (Group F)FR-LSH minimumPublic assembly, evacuation visibility
Hospital (Group C-1)HFFR (IS 17048:2018)Halogen-free mandated for ICU, OT, patient corridors
Airport, metro station, public assemblyHFFRCrowded escape, electronic equipment protection
Data centreHFFRElectronics survival post-event
AC compressor / high-ambient circuitHRFR85 °C conductor temperature
Specialised residential premiumHR-FR-LSHPolycab Green Wires only
Fire-pump feeder, lift-recall, smoke-extraction controlNOT THIS PAGE — Fire Survival cable to BS 6387 / IEC 60331 / IS 17505Reaction-to-Fire grades do not satisfy circuit-integrity requirement
A consultant who specifies "HFFR cable for the fire pump" has not specified a fire-pump cable — the fire pump needs a Fire Survival cable.

How fire-performance is tested

IS 694:2010 and IS 17048:2018 reference IEC test methods directly (with parallel IS 10810 methods for Indian-witnessed BIS testing). The four families of tests are:

TestWhat it measuresStandard
Single-cable flame propagationA 600 mm cable sample held vertically is exposed to a 1 kW propane flame for 60–480 s; char must not exceed 50 mm above the burner.IEC 60332-1-2
Bunched-cable flame propagationA 3.5 m vertical ladder of bunched cables is ignited; the char height after a defined burn time classifies the bundle as Cat A / B / C / D. FR-LSH and HFFR cables must pass at least Cat B.IEC 60332-3-22 / -23 / -24
Halogen acid gas (HCl)1 g of compound is burned in a tube furnace at 800 °C; evolved HCl is absorbed and titrated. Reported as mass %.IEC 60754-1 (mass), IEC 60754-2 (pH + conductivity)
Smoke densityA 1 m horizontal cable sample is burned in a 27 m³ cube under defined conditions; light transmittance across the diagonal is measured.IEC 61034-1 / IEC 61034-2
Oxygen indexThe minimum %O₂ in an O₂/N₂ mixture that sustains combustion of a vertical specimen.IS 10810 Pt 58 / ISO 4589-2
All five are type-test requirements in IS 694:2010 and IS 17048:2018. BIS-licensed manufacturers must hold a current type-test report against the relevant clauses for their CM/L licence to remain valid.

Brand product lines and which grade they cover

Listed alphabetically by brand. Verify the BIS CM/L licence number against the brand's current ISI marking on bis.gov.in before procurement.

BrandProduct lineGrade(s)
FinolexFinolex FR / Finolex FR-LSHFR, FR-LSH
HavellsLife Line+ S3HRFR (IS 694:2010, 85 °C HR PVC)
HavellsLife GuardFR-LSH (IS 694:2010, HCl < 15%)
HavellsLife ShieldHFFR (IS 17048:2018, HCl < 0.5%)
KEIHOMECABFR (IS 694:2010)
KEICONFLAMEFR-LSH (IS 694:2010, HCl < 15%)
KEIBANFIREHFFR (IS 17048:2018, HCl < 0.5%)
National CablesNational FR / National FR-LSHFR, FR-LSH
PolycabPolycab FR / FR-LSHFR, FR-LSH
PolycabGreen WiresHR-FR-LSH (IS 694:2010, HR PVC + HCl < 15%)
RR KabelRR FR / FR-LSH / HFFRFR, FR-LSH, HFFR
Alphabetical, not a recommendation. Verify IS standard, BIS licence and type-test certificate in the latest OEM catalogue before specifying.

Frequently asked questions

What is the difference between FR and FR-LSH?
Both are IS 694:2010. FR requires IEC 60332-1 flame retardance and oxygen index ≥ 29%, but does not regulate HCl or smoke density. FR-LSH adds two requirements: HCl < 15% per IS 10810 / IEC 60754, and improved smoke density per IEC 61034. FR-LSH is typically 8–15% above FR at list.
What is the difference between FR-LSH and HFFR?
They are governed by different Indian standards. FR-LSH is IS 694:2010 with HCl 60% at 3 m, and oxygen index ≥ 30%. The HCl ceiling ratio between the two is 30 : 1.
What does HFFR mean? (a.k.a. LSZH / ZHFR / LS0H)?
HFFR stands for *Halogen-Free Flame-Retardant*. The same product is marketed internationally as LSZH (Low Smoke Zero Halogen), LS0H (Low Smoke Zero Halogen, with a numeric zero), or ZHFR (Zero Halogen Flame Retardant). In India the standard is IS 17048:2018, with HCl < 0.5% and smoke density per IEC 61034.
Is FR-LSH a fire-survival cable?
No. FR-LSH is a *Reaction to Fire* grade — it controls smoke and acid-gas evolution while burning but does not maintain circuit integrity. *Fire Survival* cables are a separate class certified to BS 6387 (categories C/W/Z), IEC 60331-21 or IS 17505 — typically mineral-insulated or mica-tape constructions used for fire-pump power, lift-recall, smoke extraction and emergency lighting. Specifying FR-LSH on a fire-survival circuit is a non-compliance.
What is the HCl emission limit for FR-LSH?
Less than 15% by mass when tested per IS 10810 / IEC 60754-1, as required by IS 694:2010 for the FR-LSH grade. The plain FR grade has no HCl upper limit; HFFR (IS 17048:2018) tightens the limit to less than 0.5%.
What is the smoke density limit for HFFR?
IS 17048:2018 (referencing IEC 61034-2) requires light transmittance greater than 60% at 3 m in the standard 27 m³ smoke cube during the burn of a 1 m cable sample. This is the figure used for evacuation-visibility design in NBC 2016 escape routes.
Which IS standard covers HFFR cable?
IS 17048:2018 — the Indian Standard for halogen-free flame-retardant insulated cables. It is a separate standard from IS 694:2010, has a separate BIS licence (different CM/L number), and prescribes its own type tests for HCl, smoke density, oxygen index and bunched-cable flame propagation (IEC 60332-3).
Is HRFR the same as FR-LSH?
No. HRFR is IS 694:2010 FR-grade insulation made with heat-resistant 85 °C PVC — it raises the continuous conductor temperature from 70 °C to 85 °C for use on AC compressor circuits, attic runs and high-ambient locations. It does not improve HCl or smoke density. FR-LSH is IS 694:2010 FR-grade with HCl < 15% — it improves smoke and halogen at the standard 70 °C conductor temperature. They solve different problems and are sometimes combined as HR-FR-LSH (Polycab Green Wires).
What test method verifies HFFR compliance?
IS 17048:2018 references four type tests: IEC 60332-1 (single-cable flame), IEC 60332-3 (bunched-cable flame, typically Category B or better), IEC 60754-1 for HCl mass percentage and IEC 60754-2 for smoke pH and conductivity, and IEC 61034-2 for smoke density (light transmittance > 60% at 3 m). Oxygen index per IS 10810 Pt 58 / ISO 4589-2 must be ≥ 30%. BIS licensees must hold a current type-test report against all four clauses.
Why does NBC 2016 mandate HFFR for hospitals?
Two reasons. Patient evacuation in ICU, OT and ward corridors depends on visibility — HFFR's > 60% light transmittance at 3 m keeps escape routes navigable. Electronic equipment survival — monitors, ventilators, switchgear and BMS are corroded by HCl mist within minutes of a PVC fire even after extinguishment; HFFR's HCl < 0.5% ceiling prevents this. NBC 2016 Part 4 references both for Group C-1 occupancies.
What is the oxygen index of HFFR vs FR?
FR (IS 694:2010): oxygen index ≥ 29%. HFFR (IS 17048:2018): oxygen index ≥ 30%. Both are well above the ~21% atmospheric oxygen level, so neither sustains self-combustion once the external ignition source is removed. Plain PVC is ~21–23%. Measured per IS 10810 Pt 58 / ISO 4589-2.
Does HFFR cable cost more than FR?
Yes. Indicative list-price premium over plain FR, April 2026: FR-LSH +8–15%, HRFR +5–10%, HFFR +25–40%. The HFFR premium reflects polyolefin compound cost and the separate IS 17048:2018 BIS licence. For current side-by-side comparison across brands, see the FR / FR-LSH / HFFR category pages.
Stay current · B2B only

Get the new price list the day brands publish it

One short email per brand each time we verify a fresh list. No marketing, no resharing. Unsubscribe in one click.

✓ Subscribed. Optional: complete your profile so update emails can be prioritised for your role and region.

Download Price List →Free · 7 brands · 2026 PDF